<< Contents << Workbar << WorkBar Tabs << Trigger Tab
 
Ambiguous Trigger Values
 
The Trigger Values in any TriggerForm must use hexadecimal or binary characters.
 
The "anything" character ("x") is also allowed except with Range Events.
 
However, the "?" ambiguous character may automatically appear in hexadecimal trigger values.
 
The ambiguous character represents ambiguous trigger values the match more than one input value..
 
But unlike the "anything" character, ambiguous trigger values do not match all input values.
 
The "?" character warns you the trigger should be viewed in binary rather than hexadecimal.
 
Each binary character represents 1 channel. Each hex character represents 4 channels. If you edit a trigger value in binary, set some channels to 0 or 1, leave other channels as "x", then switch to the hex display, the "?" character will be displayed for the ambiguous hex character.
 
The "?" character cannot be entered from the keyboard. The GoLogic7 software automatically displays this value when needed.
 